Technology functions
CPU 317T: Technology Functions
6-66 A5E00251798-03
ErrorID
Error message Description / to correct or avoid error
8055
Saving motion not allowed in current
state
A save command can not be accepted at the current axis
state. Reasons:
The axis is to be synchronized, or this synchronization
process is currently busy.
Axis moves in synchronism.
8083 DB is not a technology DB
The DB specified at input parameter Axis or the
technology DB were not found.
8084 Invalid technology DB A technology object does not exist in the PLC for the
technology DB specified at input parameter Axis.
Download the current technology to the PLC, or
change the DB number at input parameter Axis.
The user has written invalid data to the technology DB
specified at input parameter Axis.
In "Technology Objects Management", delete and then
recreate the technology DB.
808B Parameter value of invalid REAL
format
Invalid floating-point format of at least one input parameter
value.
Check the input parameter values or the instance DB
data. Invalid values can not be indicated in floating-point
format. They are shown on hexadecimal format
(DW16# ...).